Regenwassernutzung/en: Unterschied zwischen den Versionen
(Die Seite wurde neu angelegt: „Similarly, this is also in '''regions with defined dry and rainy seasons'''. If the total water needs for the dry season were to be collected in the rainy seas…“) |
|||
(67 dazwischenliegende Versionen von 2 Benutzern werden nicht angezeigt) | |||
Zeile 1: | Zeile 1: | ||
<languages /> | <languages /> | ||
− | According to the European Drinking Water Directive <ref name="Europäische Trinkwasserverordnung">European Drinking Water Directive</ref>water in households, which is not used for drinking or bodily hygiene, can be replaced with so-called non-potable water. This non-potable water can be relatively easily collected from roof runoff water. Roof runoff is rainwater that has come from roof surfaces. At minimum non-potable water can be used for toilet flushing, laundry washing or for irrigation purposes. In this way a savings-conscious household can save up to 50 L of drinking water per person every day. Considering the usage in Germany, this constitutes around 50% of the total usage. | + | According to the European Drinking Water Directive <ref name="Europäische Trinkwasserverordnung">European Drinking Water Directive</ref> water in households, which is not used for drinking or bodily hygiene, can be replaced with so-called non-potable water. This non-potable water can be relatively easily collected from roof runoff water. Roof runoff is rainwater that has come from roof surfaces. At minimum non-potable water can be used for toilet flushing, laundry washing or for irrigation purposes. In this way a savings-conscious household can save up to 50 L of drinking water per person every day. Considering the usage in Germany, this constitutes around 50% of the total usage. |
− | With today’s technology, e.g. the [https://www.intewa.de/en/products/purain/ PURAIN] rainwater filter and [https://www.intewa.de/en/products/aqualoop/ AQUALOOP ultrafiltration] and UV disinfection, the possibilities for using rainwater for new usages, i.e. with some treatment so that | + | With today’s technology, e.g. the [https://www.intewa.de/en/products/purain/ PURAIN] rainwater filter and [https://www.intewa.de/en/products/aqualoop/ AQUALOOP ultrafiltration] and UV disinfection, the possibilities for using rainwater for new usages, i.e. with some treatment so that drinking water quality is achieved and can therefore be used for bodily hygiene or [[Wasseraufbereitung_und_Grauwassernutzung/en#Potable_water_systems|drinking water]]. The compliance and validation of the water quality is ordinarily the obligation of the individual operator. |
'''Usage possibilities:''' | '''Usage possibilities:''' | ||
Zeile 105: | Zeile 105: | ||
==Catchment areas== | ==Catchment areas== | ||
− | [[Datei: | + | [[Datei:Niederschlagsmenge_en.jpg|miniatur|300px ]] |
The rainwater yield depends on the size and type of the connected roof surfaces and the precipitation amount. If possible, all existing sealed surfaces and roof areas should be connected to achieve the highest possible yield. Different types of roofing materials differ in both their flow characteristics as well as in the potential contamination of the gathered water gathered. | The rainwater yield depends on the size and type of the connected roof surfaces and the precipitation amount. If possible, all existing sealed surfaces and roof areas should be connected to achieve the highest possible yield. Different types of roofing materials differ in both their flow characteristics as well as in the potential contamination of the gathered water gathered. | ||
Zeile 125: | Zeile 125: | ||
=Components of a rainwater harvesting system= | =Components of a rainwater harvesting system= | ||
− | =Filtration= | + | ==Filtration== |
[[Datei:Bachlauf.jpg |rechts | miniatur | Stream course]] | [[Datei:Bachlauf.jpg |rechts | miniatur | Stream course]] | ||
See also [https://www.intewa.de/en/online-planner/ Online Planner] | See also [https://www.intewa.de/en/online-planner/ Online Planner] | ||
Zeile 144: | Zeile 144: | ||
[[Datei:PR Filterwirkungsgrad.png|miniatur|300px|Filter efficiencies]] | [[Datei:PR Filterwirkungsgrad.png|miniatur|300px|Filter efficiencies]] | ||
− | A self-cleaning, fine filter is today recognized as an important component of modern rainwater harvesting. Best results are obtained with a sieve width of about 0.8 mm. Entry of contaminants into the rainwater storage and maintenance intervals are minimized. Particular care should be taken that the sieve used is arranged in a trough, as demonstrated by the [ | + | A self-cleaning, fine filter is today recognized as an important component of modern rainwater harvesting. Best results are obtained with a sieve width of about 0.8 mm. Entry of contaminants into the rainwater storage and maintenance intervals are minimized. Particular care should be taken that the sieve used is arranged in a trough, as demonstrated by the [https://www.intewa.de/en/products/purain/downloads/ test results of some rainwater filters]. There are self-cleaning rainwater filters on the market, with which about 50% of the precious water discards into the overflow, a catastrophic loss! |
'''Collecting''' | '''Collecting''' | ||
Zeile 164: | Zeile 164: | ||
===Floating suction filter=== | ===Floating suction filter=== | ||
− | [[Datei:RWN_schwimmendeAnsaugfilterung.jpg|miniatur|Floating suction filter]] | + | [[Datei:RWN_schwimmendeAnsaugfilterung.jpg|miniatur|200px|Floating suction filter]] |
[https://www.intewa.de/en/products/rainmaster/accessories/floating-suction-filter/ Floating extraction with suction filtration] ensures that the pump always draws the cleanest water from the storage. If however, coarse particles entered the tank, then the floating extraction retains them and protects the pump. The suction filter should not be too fine-meshed to prevent blocking by biofouling. This blocking can rapidly develop to defects in the pump. The ideal mesh size of the suction filter is around 1 mm. | [https://www.intewa.de/en/products/rainmaster/accessories/floating-suction-filter/ Floating extraction with suction filtration] ensures that the pump always draws the cleanest water from the storage. If however, coarse particles entered the tank, then the floating extraction retains them and protects the pump. The suction filter should not be too fine-meshed to prevent blocking by biofouling. This blocking can rapidly develop to defects in the pump. The ideal mesh size of the suction filter is around 1 mm. | ||
Zeile 174: | Zeile 174: | ||
===Disinfection=== | ===Disinfection=== | ||
− | See INTEWA WIKI guidelines for [Wasseraufbereitung_und_Grauwassernutzung/en|water treatment and greywater recycling] | + | See INTEWA WIKI guidelines for [[Wasseraufbereitung_und_Grauwassernutzung/en|water treatment and greywater recycling]] |
===Sedimentation=== | ===Sedimentation=== | ||
− | [[Datei:RWN_Sedimentation.jpg|rechts|miniatur|Inlet calming]] | + | [[Datei:RWN_Sedimentation.jpg|rechts|miniatur|200px|Inlet calming]] |
The inflowing water may still contain fine substances, which are not retained by the filter. These sedimentation constituents gradually settle down on the bottom of the storage with time, where some additional biological self-cleaning effects are active. To avoid dispersion of the accruing sedimentation layer, the inflow into the cistern should be done through an inlet calmer. | The inflowing water may still contain fine substances, which are not retained by the filter. These sedimentation constituents gradually settle down on the bottom of the storage with time, where some additional biological self-cleaning effects are active. To avoid dispersion of the accruing sedimentation layer, the inflow into the cistern should be done through an inlet calmer. | ||
Zeile 190: | Zeile 190: | ||
===Above-ground tank=== | ===Above-ground tank=== | ||
− | [[Datei:RWN Oberirdischer speicher.png| | + | [[Datei:RWN Oberirdischer speicher.png|200px| miniatur|Above-ground tank]] |
Freely erectable, above-ground tanks can be assembled in the garden, basement or on the roof of a house. They are often used when there is no possibility for underground installation of a tank, such as retrofitting in rocky ground or too narrow construction areas. | Freely erectable, above-ground tanks can be assembled in the garden, basement or on the roof of a house. They are often used when there is no possibility for underground installation of a tank, such as retrofitting in rocky ground or too narrow construction areas. | ||
The tank must be statically dimensioned in such a way that it can withstand the water pressure permanently without deformation. | The tank must be statically dimensioned in such a way that it can withstand the water pressure permanently without deformation. | ||
− | + | ''Note:'' | |
Most underground tanks cannot be freely erected. | Most underground tanks cannot be freely erected. | ||
Zeile 209: | Zeile 209: | ||
===GRP tank (glass-reinforced plastic)=== | ===GRP tank (glass-reinforced plastic)=== | ||
[[Datei:RWN gfk speicher.png |300px|miniatur|GRP tank]] | [[Datei:RWN gfk speicher.png |300px|miniatur|GRP tank]] | ||
− | Glass-reinforced plastic tanks are recommended for large storage volumes up to about 250 m³ mostly in the commercial sector. They can be made of one piece. Production is relatively flexible, so that requirements of larger construction projects can be catered to, for example heavy loads of up to SLW60 (60 t truck trafficability), flexible connection choices, integration of additional manhole shafts, fittings, pipes, internal partitions etc. These tanks are also suited as retention tanks or fire-fighting water tanks. | + | Glass-reinforced plastic tanks are recommended for large storage volumes up to about 250 m³ mostly in the commercial sector. They can be made of one piece. Production is relatively flexible, so that requirements of larger construction projects can be catered to, for example heavy loads of up to SLW60 (60 t truck trafficability), flexible connection choices, integration of additional manhole shafts, fittings, pipes, internal partitions etc. These tanks are also suited as [[Versickerung_und_Retention/en|retention tanks]] or fire-fighting water tanks. |
===Concrete tank=== | ===Concrete tank=== | ||
Zeile 221: | Zeile 221: | ||
[[Datei:RWN Tunnelsystem.png|rechts|300px |miniatur| Tunnel system]] | [[Datei:RWN Tunnelsystem.png|rechts|300px |miniatur| Tunnel system]] | ||
− | If special designs and sizes are requested for rainwater storage, then it may be appropriate to use plastic elements for rainwater infiltration and retention. DRAINMAX tunnel elements for instance can be installed in an enclosed sheet basin. The storage volume is then made up of the void volume in the backfill material and the storage volume of the tunnel. | + | If special designs and sizes are requested for rainwater storage, then it may be appropriate to use plastic elements for rainwater [[Versickerung_und_Retention/en|infiltration and retention]]. DRAINMAX tunnel elements for instance can be installed in an enclosed sheet basin. The storage volume is then made up of the void volume in the backfill material and the storage volume of the tunnel. |
=Planning and dimensioning= | =Planning and dimensioning= | ||
Zeile 234: | Zeile 234: | ||
For larger projects, perform a calculation for optimal storage sizes utilizing long-term rain data with the [[#Storage simulation with software|Rainplaner Software]]. | For larger projects, perform a calculation for optimal storage sizes utilizing long-term rain data with the [[#Storage simulation with software|Rainplaner Software]]. | ||
− | In order to calculate the optimal storage size, the relationship between rainwater yield and [[Non-potable water requirement|non-potable water requirement]] needs to be determined. | + | In order to calculate the optimal storage size, the relationship between rainwater yield and [[#Non-potable water requirement|non-potable water requirement]] needs to be determined. |
==Rainwater yield== | ==Rainwater yield== | ||
Zeile 244: | Zeile 244: | ||
|- | |- | ||
|} | |} | ||
− | |||
[[Datei:RWN ProjezierteDachflaeche.png|300px |miniatur| Projected roof area]] | [[Datei:RWN ProjezierteDachflaeche.png|300px |miniatur| Projected roof area]] | ||
Zeile 287: | Zeile 286: | ||
==Non-potable water requirement== | ==Non-potable water requirement== | ||
− | [[Datei:Wasserbedarf Uni Oldenburg.png|miniatur|300px| Water requirement in litre per person and day: a. Drinking; b. Cooking; c. Dishwasher; d. Washing; e. Teeth brushing; f. Bathing - two times a week; g. Showering - two times a week; h. Toilet; i. Washing machine; j. House cleaning; k. Car washing; l. Flower watering; m. Garden irrigation]] | + | [[Datei:Wasserbedarf Uni Oldenburg.png|miniatur|300px| Water requirement in litre per person and day: a. Drinking; b. Cooking; c. Dishwasher; d. Washing; e. Teeth brushing; f. Bathing - two times a week; g. Showering - two times a week; h. Toilet; i. Washing machine; j. House cleaning; k. Car washing; l. Flower watering; m. Garden irrigation]]Source <ref name="Uni OL">DIN 1989-1</ref> |
The non-potable requirement depends on the connected fixtures and their usage. Some average values are summarized in the table below for the requirement per person and day: | The non-potable requirement depends on the connected fixtures and their usage. Some average values are summarized in the table below for the requirement per person and day: | ||
Zeile 340: | Zeile 339: | ||
==Tank sizes== | ==Tank sizes== | ||
− | [[Datei: | + | [[Datei:Speichergroesse_en.png|300px |miniatur|Tank size]] |
'''Yield = Requirement'''<br /> | '''Yield = Requirement'''<br /> | ||
Zeile 378: | Zeile 377: | ||
|colspan="2"|* The dimensioning of the storage volume follows the 5% rule: | |colspan="2"|* The dimensioning of the storage volume follows the 5% rule: | ||
|- | |- | ||
− | | '''Storage volume:''' 0.05 x 59 m³ + 300 L = || '''3. | + | | '''Storage volume:''' 0.05 x 59 m³ + 300 L = || '''3.25 m³''' |
|- | |- | ||
|} | |} | ||
Zeile 387: | Zeile 386: | ||
Instead of using average precipitation values, actual rain events for every day are considered. Furthermore, the runoff retentions of different roof materials as well as the overflows of the storage during heavy rain events are specifically modelled. | Instead of using average precipitation values, actual rain events for every day are considered. Furthermore, the runoff retentions of different roof materials as well as the overflows of the storage during heavy rain events are specifically modelled. | ||
− | [[Datei: | + | [[Datei:Speichersimulation.png|center|600px]] |
In the displayed trend line, the seasonal variations are identified. In optimal situations during the entire year the water level stays at an average value. A few storage overflows during the year are not a problem as they remove surface contaminants from the water surface. | In the displayed trend line, the seasonal variations are identified. In optimal situations during the entire year the water level stays at an average value. A few storage overflows during the year are not a problem as they remove surface contaminants from the water surface. | ||
Zeile 398: | Zeile 397: | ||
In order to guarantee that even in dry years the surface contaminants are washed away 3 to 5 times in the overflow the storage should not be chosen as too large. | In order to guarantee that even in dry years the surface contaminants are washed away 3 to 5 times in the overflow the storage should not be chosen as too large. | ||
− | Pure irrigation is something else entirely. Here it can make sense and is wished that rainwater during rainy periods is collected for use during dry times. This leads to a much larger storage volume. | + | '''Pure irrigation''' is something else entirely. Here it can make sense and is wished that rainwater during rainy periods is collected for use during dry times. This leads to a much larger storage volume. |
Similarly, this is also in '''regions with defined dry and rainy seasons'''. If the total water needs for the dry season were to be collected in the rainy season, the rainwater storage would have to be around 6-times as big. Alternatively, thought can be given to only using the rainwater system during the rainy season based on economic reasons since a much smaller storage could be operated. | Similarly, this is also in '''regions with defined dry and rainy seasons'''. If the total water needs for the dry season were to be collected in the rainy season, the rainwater storage would have to be around 6-times as big. Alternatively, thought can be given to only using the rainwater system during the rainy season based on economic reasons since a much smaller storage could be operated. | ||
− | == | + | ==Installation instructions for rainwater tanks== |
− | [[Datei:RWN Einbauhinweis RWSpeicher.jpg |300px|miniatur| | + | [[Datei:RWN Einbauhinweis RWSpeicher.jpg |300px|miniatur|Installation instruction rainwater tanks]] |
− | + | It is important to determine the heights of the connections and installation depth for the cistern and execution of the groundwork. The necessary connection sizes of the tanks are taken from the technical product sheets. The discharge pipe must be laid below the frost-zone (in many regions in Germany e.g. 80 cm) with a 1% grade. | |
− | |||
− | + | The installation depth is determined as follows: | |
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
− | | | + | | Frost depth pipe installation '''F''' || e.g. 80 cm |
|- | |- | ||
− | | + | + | | + necessary pipe grade '''G''' || e.g. 10 cm |
|- | |- | ||
− | | + | + | | + inlet height on tank '''Z''' || e.g. 162 cm |
|- | |- | ||
− | | = | + | | = installation depth of the tank '''E''' || e.g. 252 cm |
|- | |- | ||
|} | |} | ||
− | + | According to the ground considerations approximately 10 cm should be excavated to prepare the subsurface for the placement of the cistern. | |
− | === | + | ===High ground water level=== |
− | + | With higher ground water levels only specially-designed cisterns can be used. Additionally a calculation of the flotation potential must be made. Many concrete tanks can be placed in ground water without additional flotation prevention due to their own weight and ground cover. Additional flotation prevention can be introduced e.g. with ground anchors. | |
− | === | + | ===Entry opening=== |
− | + | The entry opening to the storage must be kept free for later cleaning and maintenance work. To adjust to the ground level extendable dome shafts or concrete compensation rings can be used. To avoid accidents the entry must be secured with a locking lid or be so heavy that small children cannot open it. | |
− | === | + | ===Storage overflow and backwater level=== |
− | + | The height of the '''storage overflow''' is designed according to the connections oft he cistern. The storage overflow can be connected to the following drainage facilities: | |
− | * | + | * Infiltration systems |
− | * | + | * Stormwater sewers in separated systems |
− | * | + | * Mixed water systems |
− | + | Where possible the storage overflow should be connected to [[Versickerung_und_Retention/en|infiltration]] so that overflowing water refills the on-site ground water. If no infiltration is provided then a sewer connection is necessary for the overflow. If a separated system is provided the rainwater is fed to the stormwater sewer. Otherwise it should be connected to the mixed water network. | |
− | + | Rarely occurring heavy rainfall events can result in an overload of the respective drainage. The accumulated water cannot be properly released and a backup of water in the cistern occurs. Because of the possible repercussions on the storage, special attention must be made when designing a rainwater system for this situation. It must, in particular with connection to a mixed water system, that contaminated water is prevented from flowing from the sewer network to the storage. | |
− | + | The '''backwater level''' shows to which height water from the sewer network can be backed up to. The height of the backwater level is usually determined by the local authority. Otherwise, it is usually the same as the upper level of the road surface (DIN 1986). | |
− | ==== | + | ====Storage overflow above the backwater level==== |
− | [[Datei:RWN Speicherueberlauf.jpg |200px|miniatur| | + | [[Datei:RWN Speicherueberlauf.jpg |200px|miniatur|Storage overflow above the backwater level]] |
− | + | In very few cases the overflow will be above the backwater level. In this situation the overflow water can be directed straight to sewer with the given grade. Here the overflow must lie at minimum 20 cm above the backwater level. The overflow must be below the inlet pipework with a larger or same diameter as the inlet pipe. | |
− | ==== | + | ====Storage overflow under the backwater level of the stormwater sewer or infiltration system==== |
− | [[Datei:RWN SpeicherueberlaufunterhalbRSE.jpg |200px|miniatur| | + | [[Datei:RWN SpeicherueberlaufunterhalbRSE.jpg |200px|miniatur|Storage overflow under the backwater level]] |
− | + | If the overflow is not connected on the drainage system with backflow prevention, then according to DIN1989-1 a [[#Self-cleaning fine filter|backflow preventor]] must be installed so that by backup no water will enter the cistern. | |
− | ==== | + | ====Storage overflow on a mixed water system under the backwater level or connected to higher infiltration drainage==== |
− | [[Datei:RWN Mischwassersystem.jpg |200px|miniatur| | + | [[Datei:RWN Mischwassersystem.jpg |200px|miniatur|Rainwater storage as pump shaft]] |
− | ===== | + | =====Guideline according to standard DIN1989-1===== |
− | + | With connection of the storage overflow to a mixed water sewer or higher infiltration drainage a lift station must be used according to DIN1989-1. The lift station will supply the water above the backwater level by immersion pump after the maximum level is achieved. Attention must be paid so that the pressure line lies below the frost depth even in areas of elevated backwater. The backwater level can also lie within the home. The dimensioning of the pump is determined according to DIN1986-100 with r<sub>(5,100)</sub>. The immersion pump can be installed in the storage, eliminating the need for an additional pump shaft. | |
− | ===== | + | =====Practical execution===== |
− | + | Whereas with connection to a higher infiltration and retention system, a lift station is technically required without question, it is the customer who decides if a simple backflow preventer is sufficient for connection to a mixed water system. The risk of faecal contamination with backwater from the mixed water sewer is relative since generally the cistern will be full during overflows from the sewer system. Therefore the contamination from these rainfall events is severly diluted. | |
− | In | + | In practice, lift stations are hardly ever used. |
− | + | The same applies to dimensioning of lift stations since the calculation according to DIN1986-100 with r<sub>(5,100)</sub> is for very large flow rates. The flow rate can be reduced if an additional buffer volume is created to reduce the dimensioned heavy rainfall event. | |
− | + | Required '''immersion pump flow with usage as a lift station in a rainwater storage''' as an example of a heavy rainfall event from Cologne with or without buffer volume. | |
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
− | ! colspan="4"| | + | ! colspan="4"| Rainfall intensity r<sub>5</sub>, 100 = 648.5 L/(s-ha) Roof area A = 100 m² |
|- | |- | ||
|colspan="2"| V = 0 || colspan="2"| V = 1 m³ | |colspan="2"| V = 0 || colspan="2"| V = 1 m³ | ||
|- | |- | ||
− | | | + | | Pump flow [L/min] || Pump type || Pump flow [L/min] || Pump type |
|- | |- | ||
| 389|| BIOX 400/12 || 195||DRENOX 250/10 | | 389|| BIOX 400/12 || 195||DRENOX 250/10 | ||
|} | |} | ||
− | + | The suggested pumps are considered with a total supply head (H<sub>geo</sub> + H<sub>loss</sub>) of max. 2m. | |
− | (H<sub>geo</sub> + H<sub> | ||
− | + | Lift stations as well as [[#Self-cleaning fine filter|backflow valves]] are subject to maintenance during operation and must therefore be accessible by inspection openings. Additionally note that due to pump defects or continuing backwater no water can be pumped from the storage even though water continues in. For exceptional uncontrolled overflows with outdoor cisterns, a water outlet, which can be located in the cistern lid, is acceptable. Ingress of the water into a building e.g. through the empty pipe must be securely excluded. | |
− | ==[[Pumpen, | + | ==[[Pumpen,_Betriebs-_und_Regenwasserwerke/en|Pumps, operation and rainwater units]]== |
− | + | For dimensioning of a non-potable water pump, the following Online Tool is helpful: | |
− | [https://www.intewa.de/fileadmin/rainplanertools/ | + | [https://www.intewa.de/fileadmin/rainplanertools/en/rainmaster.html Pump dimensioning] |
− | == | + | ==Pipework and accessories== |
− | + | On the way to fixtures the rainwater flows through different pipes. The supply of the extraction points in a rainwater harvesting system is supplied over a so-called non-potable water network. The non-potable network must be made of corrosion-resistant, opaque material. The suction line of the pump should be inserted into a conduit in case of leakage. Optimal usage is with high-quality, kink-proof EPDM rubber material (PVC hose is not suggested due to chemical material softeners!). The EPDM hose cannot be closed together with suction from the pump, but guarantees the flexibilty for floating suction removal and easy installation through a conduit. EPDM hose also dampens pressure surges caused by switching on submersible pumps. In the case of suction pumps, a flexible reinforced hose should be used as insulation between the pump and the non-potable pipework. For quick-shutting fixtures or unfavourably installed pipework, an expansion vessel may be required between the controller and the fixtures. | |
− | + | Pipes and conduits should be sealed within the home using a wall bushing. | |
− | + | Pipes and conduits should be sealed within the home using a wall bushing. | |
[[Datei:RWN Leitungsnetz.jpg|600px]] | [[Datei:RWN Leitungsnetz.jpg|600px]] | ||
Zeile 501: | Zeile 498: | ||
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
− | |1. | + | |1. Rainwater unit RM-Eco || 8. Rainwater filter PURAIN |
|- | |- | ||
− | |2. | + | |2. Drinking water connection || 9. Floating suction filter |
|- | |- | ||
− | |3. | + | |3. Pressure connection set with expansion vessel || 10. Inlet calmer |
|- | |- | ||
− | |4. | + | |4. Pressure pipe to the fixtures || 11. Conduit for suction pipe and sensor cable |
|- | |- | ||
− | |5. | + | |5. Floating switch || 12. Rainwater inlet pipe |
|- | |- | ||
− | |6. | + | |6. Suction pipe || 13. Wall bushing |
|- | |- | ||
− | |7. | + | |7. Emergency overflow |
|} | |} | ||
− | = | + | =Legal regime= |
− | + | With the installation of rainwater harvesting system attention must be paid to regulations. Below are shown the German guidelines and standards. | |
− | |||
− | ==DIN | + | ==DIN and international standards:== |
{| class="wikitable" style="text-align:rechts" | {| class="wikitable" style="text-align:rechts" | ||
|- | |- | ||
− | ! | + | ! Scope !! Policy !! Content |
|- | |- | ||
− | | rowspan="11" | ''' | + | | rowspan="11" | '''Water supply''' |
− | | DIN 1989 || | + | | DIN 1989 || Standard for rainwater harvesting systems |
|- | |- | ||
− | | DIN 1989 | + | | DIN 1989 Part 1 || Planning, execution, operation and maintenance |
|- | |- | ||
− | | DIN 1989 | + | | DIN 1989 Part 2 || Rainwater filter |
|- | |- | ||
− | | DIN 1989 | + | | DIN 1989 Part 3 || Rainwater storage |
|- | |- | ||
− | | DIN 1989 | + | | DIN 1989 Part 4 || Components for control and monitoring |
|- | |- | ||
− | | DIN EN1717 || | + | | DIN EN1717 || Protection of drinking water before contamination… |
|- | |- | ||
− | | DIN 4034 | + | | DIN 4034 Part 1 || Concrete shafts |
|- | |- | ||
− | | DIN 1986-100 || | + | | DIN 1986-100 || Carryover standard: Drainage systems for buildings and properties |
|- | |- | ||
− | | DIN EN 12056 || | + | | DIN EN 12056 || Drainage inside of buildings… |
|- | |- | ||
− | | DIN EN 752 || | + | | DIN EN 752 || Drainage outside of buildings… |
|- | |- | ||
| ARCSA/ASPE/ANSI 63-2013 || Rainwater Catchment Systems | | ARCSA/ASPE/ANSI 63-2013 || Rainwater Catchment Systems | ||
|} | |} | ||
− | == | + | ==Obligations of disclosure and authorization:== |
{| class="wikitable" style="text-align:rechts" | {| class="wikitable" style="text-align:rechts" | ||
|- | |- | ||
− | ! | + | ! Scope !! Policy !! Content |
|- | |- | ||
− | | rowspan="1" | ''' | + | | rowspan="1" | '''Construction obligation''' |
− | | | + | | State construction regulation || Generally cisterns in acceptable sizes for single and two-family homes are not obligated for authorization. A description of the portion of the rainwater system for property drainage is enough regarding a drainage petition. The use of a existing tank as rainwater storage requires an authorization. |
|- | |- | ||
− | | rowspan="4" | ''' | + | | rowspan="4" | '''Water supply''' |
− | | AVBWasserV §3 || | + | | AVBWasserV §3 || Application for partial exemption from connection and usage enforcement + disclosure obligation before installation of the system with the municipal water supplier |
|- | |- | ||
− | | AVBWasserV §14 || | + | | AVBWasserV §14 || municipal water supplier is entitled to check customer system after ist commissioning |
|- | |- | ||
− | | | + | | Drinking water ordinance || Obligation to notify the health authority at start-up, decommissioning or structural changes Obligation to label the non-potable water pipes, strict separation of the drinking water and non-potable water networks |
|- | |- | ||
− | | | + | | Local drinking water statute || Possible disclosure obligation with commissioning of the system |
|} | |} | ||
− | + | Statements regarding disclosure and authorization obligations should be considered as standard. Details should be obtained from the appropriate authorities. | |
− | = | + | =Sources= |
<references /> | <references /> | ||
− | |||
− |
Aktuelle Version vom 8. November 2018, 10:52 Uhr
According to the European Drinking Water Directive <ref name="Europäische Trinkwasserverordnung">European Drinking Water Directive</ref> water in households, which is not used for drinking or bodily hygiene, can be replaced with so-called non-potable water. This non-potable water can be relatively easily collected from roof runoff water. Roof runoff is rainwater that has come from roof surfaces. At minimum non-potable water can be used for toilet flushing, laundry washing or for irrigation purposes. In this way a savings-conscious household can save up to 50 L of drinking water per person every day. Considering the usage in Germany, this constitutes around 50% of the total usage.
With today’s technology, e.g. the PURAIN rainwater filter and AQUALOOP ultrafiltration and UV disinfection, the possibilities for using rainwater for new usages, i.e. with some treatment so that drinking water quality is achieved and can therefore be used for bodily hygiene or drinking water. The compliance and validation of the water quality is ordinarily the obligation of the individual operator.
Usage possibilities:
- Toilet flushing
- Garden irrigation
- Washing machines
- Showering
- Drinking
- Cleaning purposes
- Cooling
- Process water
Advantages for the end-user
- Savings from increasing drinking and wastewater fees
- Soft rainwater is optimal for irrigation of plants
- Reduction of laundry detergent up to 50%
- No hard water buildup in washing machines and softeners are unnecessary
- Soft rainwater protects clothing
- Low-ion rainwater reduces the incidence of kidney stones
- Independence from the water provider
- No anthropogenic trace substances and medical residues
Advantages for communities
- Expenditure reduction for flood protection and avoidance
- Cost reduction for sewer construction, renewal and operation of treatment plants
- Savings potential by connection costs for new construction areas
- Secure the groundwater reservoir and therefore the drinking water supply
Basic principles
Precipitation
The precipitation <ref name="WIKI">Wikipedia</ref> is the amount of flowing water (rainwater) that has been collected in a closed basin during a specific time span from precipitation (rain, snow, hail, fog, etc.). The information is measured in litres and is correlated to square meters.
The average yearly rainfall amount
Information on average rainfall values can be obtained from the online service of weather bureaus. The average rainfall amount, e.g. in Germany is about 830 mm / year. In alpine countries 2000 mm of precipitation is very common.
average annual precipitation <ref name="DW">Wetterkontor</ref> of selected areas in Germany in mm/year
Location | mm/year | Location | mm/year | Location | mm/year | Location | mm/year |
---|---|---|---|---|---|---|---|
Aachen | 806 | Erfurt | 528 | Kassel | 696 | Neubrandenburg | 569 |
Augsburg | 824 | Essen | 893 | Kempten | 1275 | Nuremberg | 627 |
Bayreuth | 675 | Flensburg | 816 | Kiel | 752 | Passau | 934 |
Berlin | 593 | Frankfurt/M. | 655 | Cologne | 804 | Regensburg | 643 |
Bonn | 670 | Freiburg | 933 | Konstanz | 839 | Saarbrücken | 812 |
Bremen | 713 | Gera | 608 | Leipzig | 586 | Schwerin | 625 |
Chemnitz | 726 | Görlitz | 673 | Lübeck | 658 | Siegen | 1008 |
Cottbus | 573 | Greifswald | 552 | Magdeburg | 521 | Stuttgart | 675 |
Dortmund | 840 | Halle | 476 | Mainz | 587 | Uelzen | 616 |
Dresden | 668 | Hamburg | 744 | Mannheim | 642 | Ulm | 744 |
Düsseldorf | 757 | Hanover | 644 | Munich | 920 | Wittenberg | 576 |
Emden | 778 | Karlsruhe | 740 | Münster | 747 | Würzburg | 597 |
Seasonal distribution of precipitation
In addition to the average amount of precipitation, the seasonal distribution of precipitation is an important input parameter for tank dimensioning.
Source <ref name="Wiki-media">commons Wikimedia</ref>
Peak precipitation of rain events
In addition to the average annual precipitation and the seasonal distribution the consideration of short-term rain events is important for optimal dimensioning, particularly for pipes, rainwater filters and rainwater retention systems. Heavy rain events that occur approximately 4 to 10 times in a year, hardly contribute to water yield in most regions. For instance, heavy rain events contribute only about 3% of the total water yield in Germany. By contrast, light rain events provide about 97% of the water quantity. This knowledge is particularly important for the selection of an appropriate filter system.
Evaluation of rainfall<ref name="Uni Siegen">Siegen Forschungsstelle Wasserwirtschaft fwu Universität Siegen</ref> data for the years 1993 to 1997 by Siegen Research Center for Water Management, Research Institute for Water and Environment, University of Siegen
Rainfall | 1993 | 1994 | 1995 | 1996 | 1997 | Average | Total |
---|---|---|---|---|---|---|---|
mm/5min | % | % | % | % | % | % | % |
0.1 | 64.11 | 64.03 | 67.74 | 69.47 | 68.25 | 66.72 | 66.7 |
0.2 | 19.78 | 20.93 | 18.40 | 16.93 | 18.94 | 18.99 | 85.7 |
0.3 | 8.24 | 8.64 | 7.39 | 6.84 | 6.51 | 7.52 | 93.2 |
0.4 | 3.55 | 2.7 | 2.96 | 2.84 | 2.74 | 2.96 | 96.2 |
The table shows that more than 96% of rainfall occurs with an intensity of up to 0.4 mm / 5 min. With a roof area of 150 m², a rainfall of 0.4 mm / 5 min corresponds to an inflow of 0.2 L / s maximum.
This precipitation characteristic, that light rain events deliver > 96% of the rainfall amount – is similar worldwide. Also refer to the values of heavy precipitation values for the USA
Catchment areas
The rainwater yield depends on the size and type of the connected roof surfaces and the precipitation amount. If possible, all existing sealed surfaces and roof areas should be connected to achieve the highest possible yield. Different types of roofing materials differ in both their flow characteristics as well as in the potential contamination of the gathered water gathered.
House and garage roofs are the most suitable catchment areas for rainwater harvesting. Particularly suited are the roofs with smooth surfaces such as tiles, slate or glass. Tile and slate roofs also increase the pH value of acidic rain.
Courtyard or parking areas With connection to courtyard or parking areas additional preliminary cleaning must be done depending on the accumulation of pollutants and separators may be required in case of risk of oil contamination.
Green roofs offer a significantly lower yield due to their natural retention effect. Here particular attention must be paid to the organic load and water discolouration. With a reasonable yield and professional construction, green roofs are quite suitable as collection areas.
Bitumen roofs cause, as with all new roofs, in the beginning a yellow discolouration in the captured rainwater. In order to prevent this colour in laundry, for the first months at least, the washing machine should not be connected.
Asbestos cement roofs The asbestos cement roof must be refurbished before the water is used for example for garden irrigation, in order to avoid the danger of loose asbestos fibres.
Metal roofs Copper, zinc and lead, depending on the runoff concentration, are not suitable for irrigating crop plants. If in doubt, a water sample should be tested. This water can be readily used however without problem for watering ornamental plants, toilet flushing and for washing machines.
Components of a rainwater harvesting system
Filtration
See also Online Planner
With the following measures a good non-potable water quality can be achieved from rainwater:
- Self-cleaning fine filter
- Protection from backwater and small animals
- Skimmer overflow
- Floating suction filter
- Disinfection
- Sedimentation and biological cleaning
- Storage
If the water needs to reach drinking water quality, further treatment steps are required such as ultrafiltration and UV disinfection.
Self-cleaning fine filter
A self-cleaning, fine filter is today recognized as an important component of modern rainwater harvesting. Best results are obtained with a sieve width of about 0.8 mm. Entry of contaminants into the rainwater storage and maintenance intervals are minimized. Particular care should be taken that the sieve used is arranged in a trough, as demonstrated by the test results of some rainwater filters. There are self-cleaning rainwater filters on the market, with which about 50% of the precious water discards into the overflow, a catastrophic loss!
Collecting
It is especially important to make sure that light precipitation, which provides 97 % of water quantity, is 100% collected. With a PURAIN filter for instance, this takes place in a single collection area. Only in this way can an effective overall efficiency of > 98% be achieved. In filters without such a collection area, light precipitation always flows though the same sieve area. As a result the area quickly becomes clogged and further light rain precipitation flows into the overflow.
Self-cleaning
Heavy rain events are suitably used for self-cleaning (discharge of leaves, etc. from the collection area). Heavy precipitation events, which occur about 4 to 10 times a year (Germany) and contribute only approximately 3% of the total water yield, clean out the collection areas of for instance the PURAIN filter using turbulence, the so-called "hydraulic jump".
Protection from backwater and small animals
Clean water does not mean only to clean flowing rainwater, but also to assure that no pollution or small animals from the drainage system can enter the storage through the overflow. This is easily ensured by a non-return valve. Some filters, such as the PURAIN 100 already include these. In some countries such as Germany, the non-return valve is a requirement of the standard (DIN 1989 Part 1 prescribed non-return valve for connection of overflow to a separate system).
Skimmer overflow
An overflow skimmer removes with every storage overflow the floating surface contaminants and automatically transports them to the polluted water discharge. This is a sensible and practical measure to easily and regularly remove grease, pollen, etc. from the storage. The skimmer is already integrated in the PURAIN 100 filter.
Floating suction filter
Floating extraction with suction filtration ensures that the pump always draws the cleanest water from the storage. If however, coarse particles entered the tank, then the floating extraction retains them and protects the pump. The suction filter should not be too fine-meshed to prevent blocking by biofouling. This blocking can rapidly develop to defects in the pump. The ideal mesh size of the suction filter is around 1 mm.
Fine filter
By using the described filtration and cleaning techniques, the use of fine filters with mesh openings < 0.8 mm for toilets, washing machines and irrigation is redundant.
Finer filters may be needed for special requirements with process water. Then such a filter is to be installed on the pressure side behind the pump. During operation it is important to pay attention to regular maintenance as fine filters retain dirt. They should be opaque and care should be taken to ensure simple maintenance with provided stopcocks and ventilation.
Disinfection
See INTEWA WIKI guidelines for water treatment and greywater recycling
Sedimentation
The inflowing water may still contain fine substances, which are not retained by the filter. These sedimentation constituents gradually settle down on the bottom of the storage with time, where some additional biological self-cleaning effects are active. To avoid dispersion of the accruing sedimentation layer, the inflow into the cistern should be done through an inlet calmer.
Storage of water
In order to ensure optimal water quality proper storage of the rainwater plays a deciding role. The water is best stored cool and protected from light to prevent as little algae and bacterial growth as possible. Further the storage must be frost-protected.
The storage has a special importance in rainwater harvesting simply due to the construction size. In tropical countries with daily precipitation a tank with only a few hundred litres covers the daily needs of a single-family house. In some areas of Spain there are cisterns today with several hundred m³ of volume in order to last through prolonged dry-periods. When precipitation events are in general uniformly distributed throughout the year (e.g. Germany) and correspond well to the needs of the users, then the useful storage volumes are much smaller than often assumed. In order to determine a useful storage volume information about the quantity and distribution of precipitation as well as the needs is required. Attention must be given to continuing climate change which is resulting in longer dry-periods and accordingly larger required storage volumes.
Generally the following storage types are distinguished:
Above-ground tank
Freely erectable, above-ground tanks can be assembled in the garden, basement or on the roof of a house. They are often used when there is no possibility for underground installation of a tank, such as retrofitting in rocky ground or too narrow construction areas.
The tank must be statically dimensioned in such a way that it can withstand the water pressure permanently without deformation. Note: Most underground tanks cannot be freely erected.
Furthermore, it is important that these tanks are absolutely opaque to prevent biological growth. Freely erectable above-ground tanks are made of several materials, the most common of which are PE, PP, GRP, concrete, coated metals, but also wood and clay.
Underground tank
They are suitable for many new buildings if excavation has already been done. They can be housed under parking areas or driveways to save space.
Underground tanks must be dimensioned for decades of useful life and for soil and traffic loads. Underground tanks are made of several materials, the most common of which are PE, PP, GRP, and concrete.
PE or HDPE plastic tank
Plastic tanks are produced by various manufacturing processes. The most common method is called rotational moulding through which PE (recyclable polyethylene) is melted in a hollow form, rotated and cooled. After demoulding, the hollow body (tank) is obtained. Since the machinery costs are not particularly high, several different shapes are available on the market. The stability and quality of the storage is determined by the suitable shape, wall thickness and ribbed-structure. Most of these tanks are offered in the walkable design (no traffic loads) and with volumes from 1000 to max. 10,000 litres suitable for single-family houses. In order to obtain greater storage volumes, several tanks can be coupled together. Their low weight makes transportation cheaper than concrete tanks and easy placement in the excavation pit without a crane. Most underground plastic tanks are not suitable for high groundwater levels or cohesive soils (clay). The uniform filling and compaction with a suitable filling material for plastic tanks is a prerequisite to achieve the necessary stability.
GRP tank (glass-reinforced plastic)
Glass-reinforced plastic tanks are recommended for large storage volumes up to about 250 m³ mostly in the commercial sector. They can be made of one piece. Production is relatively flexible, so that requirements of larger construction projects can be catered to, for example heavy loads of up to SLW60 (60 t truck trafficability), flexible connection choices, integration of additional manhole shafts, fittings, pipes, internal partitions etc. These tanks are also suited as retention tanks or fire-fighting water tanks.
Concrete tank
Several concrete factories now produce monolithic concrete tanks (without junctions in water area) for rainwater harvesting in sizes of up to 20 m³. Due to the weight of tanks and the corresponding high transportation costs on special trucks with rear-mounted cranes, they are usually used within a range of a few 100 km around the production factory. Since the tanks can be directly installed in the excavation pit most suitably by the rear crane, it must be well accessible by the truck. Most concrete tanks are usually trafficable by passenger cars and with the appropriate cover even by trucks. With appropriate soil cover, the concrete tank can also be used with high groundwater. Cohesive soils are usually unproblematic. Larger volumes can be realized by coupling multiple tanks or with in-situ concrete construction. The quality of a concrete cistern is determined by the concrete quality (e.g. compressive strength class C45/55), the concrete reinforcement (steel reinforcement at least in the base and cover) and wall thickness (min. 8 cm).
Former oil and septic tanks
Sometimes even former septic tanks or old oil tanks can be retrofitted for rainwater storage. The old tanks should still be in good condition otherwise the retrofit is more expensive and elaborate than using a new tank. A coating for a steel tank can quickly become more expensive than a new rainwater tank.
Tunnel system
If special designs and sizes are requested for rainwater storage, then it may be appropriate to use plastic elements for rainwater infiltration and retention. DRAINMAX tunnel elements for instance can be installed in an enclosed sheet basin. The storage volume is then made up of the void volume in the backfill material and the storage volume of the tunnel.
Planning and dimensioning
For dimensioning a rainwater harvesting system, the following Online Tools are very helpful:
Dimensioning cisterns
For larger projects, perform a calculation for optimal storage sizes utilizing long-term rain data with the Rainplaner Software.
In order to calculate the optimal storage size, the relationship between rainwater yield and non-potable water requirement needs to be determined.
Rainwater yield
For a rough calculation that is enough for most storage size dimensioning, the following calculation is reliable for an average yearly rainwater yield:
Rainwater yield = roof area x precipitation amount x runoff coefficient x filter efficiency |
---|
Roof area: The roof area includes the projected roof area in m² including all overhangs.
Precipitation amount: The average annual precipitation in mm/year is shown in the overview map. More detailed information can be obtained from the respective weather bureau.
Runoff coefficient: The runoff coefficient determines the proportion of rainfall from the total precipitation that is actually released by the roof. Described here is a very simplified simulation of the retention in different roofing materials, which have been tested in practice.
Runoff coefficients for different roof materials according to DIN 1989 Part 1:
Roof material | Runoff coefficient |
---|---|
Pitched hard roof | 0.8 |
Gravel / non-gravel flat roof | 0.6 / 0.8 |
Intensive / extensive green roof | 0.3 / 0.5 |
Filter efficiency: An effective filter efficiency around 0.98 is calculated with use of a PURAIN filter.
Example 1
Calculation of rainwater yield |
---|
* Single-family house with 100 m² roof area and clay-brick roof |
* Annual precipitation = 750 mm/year |
* Runoff coefficient = 0.8 |
* Filter efficiency = 0.98 |
=>Rainwater yield = 100 m² x 750 mm/year x 0.8 x 0.98 x 10-3 = 59 m³/year |
Non-potable water requirement
Source <ref name="Uni OL">DIN 1989-1</ref>
The non-potable requirement depends on the connected fixtures and their usage. Some average values are summarized in the table below for the requirement per person and day:
Daily average consumption / person | ||
---|---|---|
House | Toilet flushing | 30 litres |
Washing machine | 10 litres | |
Garden irrigation | 60 L/m² year | |
Cleaning purposes | 6 litres | |
Showering, bathing, hand washing | 59 litres | |
Drinking water | 1 litre | |
Office building | Cleaning purposes | |
Toilet flushing | 12 litres | |
School / sports hall | Toilet flushing | 6 litres |
Sprinkler system | 200 L/m² |
Example 2
Calculation of non-potable water requirement | ||
---|---|---|
* * daily requirement of non-potable water in a 4-person household: | ||
* Toilet flushing | 30 litres / person x 4 people = | 120 litres |
* Washing machine | 10 litres / person x 4 people = | 40 litres |
* Garden irrigation | 1 litre / person x 4 people = | 4 litres |
=> Total non-potable water requirement per day: | 164 litres | |
=> Annual requirement: | 164 litres/day x 365 days = | 60 m³ |
When compared with the rainwater yield of 59 m³ determined in Example 1 for a single-family house, it is seen that almost the total requirement of the toilet, washing machine and garden can be covered by the average rainwater yield.
Tank sizes
Yield = Requirement
If the rainwater yield covers the non-potable water requirement, then an easy dimensioning value of 5% of the average yearly rainwater yield is reliable. In the image attention must be paid to the non-used portion of the tank (e.g. 300 litres in a 3000 litre tank) found between the tank bottom and the suction inlet.
Yield << Requirement
Tanks with smaller dimensions are preferred when the rainwater yield is permanently much lower than the non-potable water requirement. In this case, a tank volume of 3% of the average annual rainwater yield is sufficient. If there is low yield, then it should be initially checked whether other roof areas (e.g. neighbouring buildings) can be connected to the system. If this is not possible, then it may be appropriate to connect only some of the consumption points to rainwater harvesting to reduce the necessary drinking water backup.
Yield >> Requirement
In this situation the dimensioning primarily aligns itself along the non-potable water requirement and can with around 5% of the yearly requirement roughly estimated.
Example 3
Determination of the required storage volume for a single-family house. | |
---|---|
The data for this example is taken from Example 1 and Example 2. | |
* Roof area (brick): | 100 m² |
* Yearly precipitation: | 750 mm |
* Runoff coefficient incl. filter efficiency: | 78.4 % |
=> Rainwater yield: | 59 m³/year |
Number of users: | 4 people |
Connected fixtures: | Toilet, Washing machine, garden irrigation |
=>Non-potable water requirement: | 60 m³/year |
* The dimensioning of the storage volume follows the 5% rule: | |
Storage volume: 0.05 x 59 m³ + 300 L = | 3.25 m³ |
Storage simulation with software
Larger construction projects and commercial non-potable water usage should have a more specific requirement analysis done, e.g. the influences of seasonal variations, vacation periods, etc. Here for example the simulation software RAINPLANER can be utilized.
Instead of using average precipitation values, actual rain events for every day are considered. Furthermore, the runoff retentions of different roof materials as well as the overflows of the storage during heavy rain events are specifically modelled.
In the displayed trend line, the seasonal variations are identified. In optimal situations during the entire year the water level stays at an average value. A few storage overflows during the year are not a problem as they remove surface contaminants from the water surface.
Economical storage volume
Simulations, varying precipitation amounts and the amount of overflow water considered prove that the storage should not be chosen as too large. The coverage ratio in the figure describes the portion of non-potable water requirement that can be covered by rainwater. For Example 3 this ratio is displayed in the graphic as dependent on the storage volume. The maximal possible targeted coverage ratio is 94 %. To achieve this value, an exceedingly large tank would be needed. In practice, a tank with 3.5 m³ would be installed that can almost cover 80 % of the non-potable water requirement with rainwater. An unnecessary enlargement of the storage volume would increase the investment costs.
In order to guarantee that even in dry years the surface contaminants are washed away 3 to 5 times in the overflow the storage should not be chosen as too large.
Pure irrigation is something else entirely. Here it can make sense and is wished that rainwater during rainy periods is collected for use during dry times. This leads to a much larger storage volume.
Similarly, this is also in regions with defined dry and rainy seasons. If the total water needs for the dry season were to be collected in the rainy season, the rainwater storage would have to be around 6-times as big. Alternatively, thought can be given to only using the rainwater system during the rainy season based on economic reasons since a much smaller storage could be operated.
Installation instructions for rainwater tanks
It is important to determine the heights of the connections and installation depth for the cistern and execution of the groundwork. The necessary connection sizes of the tanks are taken from the technical product sheets. The discharge pipe must be laid below the frost-zone (in many regions in Germany e.g. 80 cm) with a 1% grade.
The installation depth is determined as follows:
Frost depth pipe installation F | e.g. 80 cm |
+ necessary pipe grade G | e.g. 10 cm |
+ inlet height on tank Z | e.g. 162 cm |
= installation depth of the tank E | e.g. 252 cm |
According to the ground considerations approximately 10 cm should be excavated to prepare the subsurface for the placement of the cistern.
High ground water level
With higher ground water levels only specially-designed cisterns can be used. Additionally a calculation of the flotation potential must be made. Many concrete tanks can be placed in ground water without additional flotation prevention due to their own weight and ground cover. Additional flotation prevention can be introduced e.g. with ground anchors.
Entry opening
The entry opening to the storage must be kept free for later cleaning and maintenance work. To adjust to the ground level extendable dome shafts or concrete compensation rings can be used. To avoid accidents the entry must be secured with a locking lid or be so heavy that small children cannot open it.
Storage overflow and backwater level
The height of the storage overflow is designed according to the connections oft he cistern. The storage overflow can be connected to the following drainage facilities:
- Infiltration systems
- Stormwater sewers in separated systems
- Mixed water systems
Where possible the storage overflow should be connected to infiltration so that overflowing water refills the on-site ground water. If no infiltration is provided then a sewer connection is necessary for the overflow. If a separated system is provided the rainwater is fed to the stormwater sewer. Otherwise it should be connected to the mixed water network.
Rarely occurring heavy rainfall events can result in an overload of the respective drainage. The accumulated water cannot be properly released and a backup of water in the cistern occurs. Because of the possible repercussions on the storage, special attention must be made when designing a rainwater system for this situation. It must, in particular with connection to a mixed water system, that contaminated water is prevented from flowing from the sewer network to the storage.
The backwater level shows to which height water from the sewer network can be backed up to. The height of the backwater level is usually determined by the local authority. Otherwise, it is usually the same as the upper level of the road surface (DIN 1986).
Storage overflow above the backwater level
In very few cases the overflow will be above the backwater level. In this situation the overflow water can be directed straight to sewer with the given grade. Here the overflow must lie at minimum 20 cm above the backwater level. The overflow must be below the inlet pipework with a larger or same diameter as the inlet pipe.
Storage overflow under the backwater level of the stormwater sewer or infiltration system
If the overflow is not connected on the drainage system with backflow prevention, then according to DIN1989-1 a backflow preventor must be installed so that by backup no water will enter the cistern.
Storage overflow on a mixed water system under the backwater level or connected to higher infiltration drainage
Guideline according to standard DIN1989-1
With connection of the storage overflow to a mixed water sewer or higher infiltration drainage a lift station must be used according to DIN1989-1. The lift station will supply the water above the backwater level by immersion pump after the maximum level is achieved. Attention must be paid so that the pressure line lies below the frost depth even in areas of elevated backwater. The backwater level can also lie within the home. The dimensioning of the pump is determined according to DIN1986-100 with r(5,100). The immersion pump can be installed in the storage, eliminating the need for an additional pump shaft.
Practical execution
Whereas with connection to a higher infiltration and retention system, a lift station is technically required without question, it is the customer who decides if a simple backflow preventer is sufficient for connection to a mixed water system. The risk of faecal contamination with backwater from the mixed water sewer is relative since generally the cistern will be full during overflows from the sewer system. Therefore the contamination from these rainfall events is severly diluted.
In practice, lift stations are hardly ever used.
The same applies to dimensioning of lift stations since the calculation according to DIN1986-100 with r(5,100) is for very large flow rates. The flow rate can be reduced if an additional buffer volume is created to reduce the dimensioned heavy rainfall event.
Required immersion pump flow with usage as a lift station in a rainwater storage as an example of a heavy rainfall event from Cologne with or without buffer volume.
Rainfall intensity r5, 100 = 648.5 L/(s-ha) Roof area A = 100 m² | |||
---|---|---|---|
V = 0 | V = 1 m³ | ||
Pump flow [L/min] | Pump type | Pump flow [L/min] | Pump type |
389 | BIOX 400/12 | 195 | DRENOX 250/10 |
The suggested pumps are considered with a total supply head (Hgeo + Hloss) of max. 2m.
Lift stations as well as backflow valves are subject to maintenance during operation and must therefore be accessible by inspection openings. Additionally note that due to pump defects or continuing backwater no water can be pumped from the storage even though water continues in. For exceptional uncontrolled overflows with outdoor cisterns, a water outlet, which can be located in the cistern lid, is acceptable. Ingress of the water into a building e.g. through the empty pipe must be securely excluded.
Pumps, operation and rainwater units
For dimensioning of a non-potable water pump, the following Online Tool is helpful:
Pipework and accessories
On the way to fixtures the rainwater flows through different pipes. The supply of the extraction points in a rainwater harvesting system is supplied over a so-called non-potable water network. The non-potable network must be made of corrosion-resistant, opaque material. The suction line of the pump should be inserted into a conduit in case of leakage. Optimal usage is with high-quality, kink-proof EPDM rubber material (PVC hose is not suggested due to chemical material softeners!). The EPDM hose cannot be closed together with suction from the pump, but guarantees the flexibilty for floating suction removal and easy installation through a conduit. EPDM hose also dampens pressure surges caused by switching on submersible pumps. In the case of suction pumps, a flexible reinforced hose should be used as insulation between the pump and the non-potable pipework. For quick-shutting fixtures or unfavourably installed pipework, an expansion vessel may be required between the controller and the fixtures. Pipes and conduits should be sealed within the home using a wall bushing.
Pipes and conduits should be sealed within the home using a wall bushing.
1. Rainwater unit RM-Eco | 8. Rainwater filter PURAIN |
2. Drinking water connection | 9. Floating suction filter |
3. Pressure connection set with expansion vessel | 10. Inlet calmer |
4. Pressure pipe to the fixtures | 11. Conduit for suction pipe and sensor cable |
5. Floating switch | 12. Rainwater inlet pipe |
6. Suction pipe | 13. Wall bushing |
7. Emergency overflow |
Legal regime
With the installation of rainwater harvesting system attention must be paid to regulations. Below are shown the German guidelines and standards.
DIN and international standards:
Scope | Policy | Content |
---|---|---|
Water supply | DIN 1989 | Standard for rainwater harvesting systems |
DIN 1989 Part 1 | Planning, execution, operation and maintenance | |
DIN 1989 Part 2 | Rainwater filter | |
DIN 1989 Part 3 | Rainwater storage | |
DIN 1989 Part 4 | Components for control and monitoring | |
DIN EN1717 | Protection of drinking water before contamination… | |
DIN 4034 Part 1 | Concrete shafts | |
DIN 1986-100 | Carryover standard: Drainage systems for buildings and properties | |
DIN EN 12056 | Drainage inside of buildings… | |
DIN EN 752 | Drainage outside of buildings… | |
ARCSA/ASPE/ANSI 63-2013 | Rainwater Catchment Systems |
Obligations of disclosure and authorization:
Scope | Policy | Content |
---|---|---|
Construction obligation | State construction regulation | Generally cisterns in acceptable sizes for single and two-family homes are not obligated for authorization. A description of the portion of the rainwater system for property drainage is enough regarding a drainage petition. The use of a existing tank as rainwater storage requires an authorization. |
Water supply | AVBWasserV §3 | Application for partial exemption from connection and usage enforcement + disclosure obligation before installation of the system with the municipal water supplier |
AVBWasserV §14 | municipal water supplier is entitled to check customer system after ist commissioning | |
Drinking water ordinance | Obligation to notify the health authority at start-up, decommissioning or structural changes Obligation to label the non-potable water pipes, strict separation of the drinking water and non-potable water networks | |
Local drinking water statute | Possible disclosure obligation with commissioning of the system |
Statements regarding disclosure and authorization obligations should be considered as standard. Details should be obtained from the appropriate authorities.
Sources
<references />