Translations:Loeschwasser/12/en

Aus INTEWA Wiki

Property protection

According to DVGW Guideline W 405, property protection is the property-specific fire water supply for buildings with a particular fire risk that goes beyond basic protection. A distinction is made between public and non-public fire water supplies. This classification is particularly important for the building permit procedure, because requirements can only be made for the non-public fire water supply.

Storage capacity

DIN 14230 distinguishes between small (75 m3 to 150 m³), medium (from more than 150 m³ to 300 m³) and large (of more than 300 m³) fire water tanks. The withdrawal piping is defined according to DIN 14244.